• JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor

JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor

No.JTG‑IR‑BS10
JTG‑IR‑BS10 dual‑band infrared flame detector adopts dual‑infrared spectrum sensing technology to capture the unique infrared flicker signal of flame for accurate open‑fire identification. Powered by DC24V, it outputs via relay dry contacts, providing fire alarm output and device fault output. With strong anti‑interference performance, it is compatible with fire alarm panels and PLC control systems, widely used in industrial workshops, boiler rooms, coating workshops, ship cabins and other areas with open‑fire hazards.
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor
  • JTG‑IR‑BS10 Dual‑Band Infrared Flame Detector, DC24V Passive Relay Dry Contact Output, Fire & Fault Signal, Industrial Marine Flame Sensor

Description

Product Parameters
Model: JTG‑IR‑BS10
Detection Principle: Dual‑band infrared spectrum detection
Operating Voltage: DC 24V
Operating Current: ≤80mA
Output: Passive relay dry contact (Fire alarm + Fault signal) 
Contact Rating: 30V DC / 1A Max
Detection Viewing Angle: 90°
Detection Distance: 0‑25m (depends on flame size) 
Response Time: 2‑10s adjustable
Operating Temperature: ‑20℃ ~ +70℃
Protection Grade: IP44
Installation: Surface mounting, circular base fixed by screws
Housing Material: Engineering plastic
Dimension: Φ100mm 
Weight: 280g

Product Advantages
Dual‑band infrared detection filters interference from lamps and sunlight to minimize false alarms
Dual relay outputs: fire alarm & fault monitoring for upper‑system status supervision
Wide temperature range, suitable for high‑/low‑temperature industrial sites
Low‑power design for long‑term continuous operation
Passive dry‑contact output compatible with most fire panels, PLC and alarm controllers
Simple structure for easy installation & wiring
Detects early open flame, insensitive to ordinary smoke


Working Principle
Open fire radiates infrared light of specific wavelengths with regular flicker. JTG‑IR‑BS10 is equipped with two infrared sensors to collect flame spectrum and flicker features. Internal MCU algorithm analyzes signals and filters interference from lamp light and sunlight. Alarm relay triggers once flame signature is confirmed. Fault relay activates when sensing windows are contaminated or hardware failure occurs.

Application Scenarios
‑ Industrial boiler rooms & heat‑treatment workshops
‑ Spraying, coating and chemical workshops
‑ Oil & gas storage areas, pump houses
‑ Ship engine rooms & hazardous cabins
‑ Waste treatment stations, energy storage power stations
‑ Protection for drying equipment and kilns
‑ Warehouses and flammable‑material storage zones

Maintenance
1. Regularly clean sensing windows from dust and grease; contamination leads to reduced sensitivity or fault
    alerts
2. Conduct quarterly function test to verify alarm & fault output circuits
3. Tighten terminal screws periodically to avoid loose connection caused by vibration
4. Do NOT clean housing with strong solvent; use clean soft cloth only
5. Avoid long‑term direct sunlight onto sensing windows to prevent false alarms
6. If frequent fault occurs, clean windows first; replace unit if cleaning does not resolve issue

Spare Parts
1. Complete JTG‑IR‑BS10 detector unit (main replacement spare part)

2. Mounting screw kit
3. Terminal accessories
Note: Separate sensor module is not available. Replace whole unit in case of sensor damage.

Acceptance
1. Power‑on check: After DC24V power supply, no fault output, unit stays in standby
2. Wiring check: Correct power polarity, no short‑circuit; no high‑voltage connected to relay dry contacts
3. Function test: Apply flame test source, detector shall trigger alarm output within specified response time
4. Fault simulation: Cover sensing windows, unit shall send fault signal
5. Mechanical check: Firm installation; sensing windows face monitored area without blockage
6. Document check: Model & specifications match purchase requirements

FAQ
Q1: Why does the detector give frequent false alarms?
① Direct sunlight or high‑temperature heat source shining on sensing windows; ② Nearby strong infrared light sources; ③ Wrong mounting angle.
Solution: Relocate unit away from direct heat and strong light.

Q2: Device keeps sending fault signal?
① Dust/grease covering sensing windows; ② Loose wiring; ③ Hardware damage.
Solution: Clean windows and tighten terminals; replace whole unit if fault persists.

Q3: Can I connect 220V sounder directly?
No. Output is passive dry contact with max rating 1A/30VDC. An intermediate relay is required for 220V load isolation.

Q4: How to understand detection distance?
Detection distance depends on flame size. Rated distance is based on standard open‑fire source; smaller flame leads to shorter effective range.

Q5: Can this detector detect smoke?
No. It is a flame detector only for open‑fire infrared signal, not sensitive to smoke.


Q6: Will reverse power supply burn the unit?
Strictly distinguish 24V positive & negative. Reverse polarity will stop device operation and may damage internal circuit over time.

Download

CONTACT US

If you have any queries, get in touch today! Don't hesitate. We try to take the extra step for our customer satisfaction.
Name
Email *
Message
Verification Code *
Click to verify
Leave a message
Name
Email *
Message
Verification Code *
Click to verify